WEATHER-RITE™ BH Technical Data


Model
 
BH-40
BH-60
BH-80
BH-100
BH-115
Minimum Length of Straight Tube*
[ft, in] A
10
20
20
30
30
Minimum Length of U-Tube*
[ft, in] B
N/A
11, 7
11, 7
16, 7
16, 7
Overall Minimum Length of Straight Tube*
[ft, in] C
10, 11
20, 11
20, 11
30, 11
30, 11
Overall Minimum Length of U-Tube*
[ft, in] D
N/A
12, 6
12, 6
17, 6
17, 6
*For additional lengths, please see the current Installation, Operation and Service Manual.
Input (Btu/h) x 1000
40
60
80
100
115
Inlet Pressure
[in wc] NG min.
4.6
4.6
4.6
4.6
4.6
 
LPG Propane min.
11
11
11
11
11
 
NG & LPG Propane max.
14
14
14
14
14
Gas Connection
NPT
½"
½"
½"
½"
½"


Model
 
BH-125
BH-140
BH-150
BH-175
BH-200
Minimum Length of Straight Tube*
[ft, in] A
40
40
50
50
60
Minimum Length of U-Tube*
[ft, in] B
21, 7
21, 7
26, 7
26, 7
31, 7
Overall Minimum Length of Straight Tube*
[ft, in] C
40, 11
40, 11
50, 11
50, 11
60, 11
Overall Minimum Length of U-Tube*
[ft, in] D
22, 6
22, 6
27, 6
27, 6
32, 6
*For additional lengths, please see the current Installation, Operation and Service Manual.
Input (Btu/h) x 1000
125
140
150
175
200
Inlet Pressure
[in wc] NG min.
4.6
4.6
4.6
5
5
 
LPG Propane min.
11
11
11
11
11
 
NG & LPG Propane max.
14
14
14
14
14
Gas Connection
NPT
½"
¾"
¾"
¾"
¾"


Weights
 
Overall Length of Tube and Accessory Package
[ft]
10
20
30
40
50
60
70
80
Hot Rolled or Aluminized Tube with Aluminum Reflector
[lb]
52
86
120
161
206
240
281
322
Aluminized Tube with Stainless Steel End Caps
[lb]
66
113
152
208
265
304
360
416
Burner
[lb]
29
29
29
29
29
29
29
29
Aluminized U-Tube with Aluminized End Caps
[lb]
19
19
19
19
19
19
19
19
Aluminized U-Tube with Stainless Steel End Caps
[lb]
20
20
20
20
20
20
20
20

General Data
Fuel
 
NG or LPG Propane
Electrical Supply
 
102 V, 60 Hz, 1 A
Heat Exchanger Tubing
 
10 ft. Sections, 4" dia, 16 Gauge, First 10 ft. ALUMI-THERM® Steel Tubing
[Remaining Hot Rolled or Heat Treated Aluminized Tubing]
Exhaust Flue
dia
4"
Reflector and End Caps
 
.024 Aluminum [Optional - .024 Stainless Steel Type 304]
Control System
 
Fully Automatic, Three-Try, 100% Shut-Off, Direct Spark Electronic Ignition Control
Approved As
 
Indoor (Vented or Unvented)
Certification
 
ANSI Z83.20 / CSA 2.34, 2.17, 2.20
Warranty
 
Three-Year Limited (Refer to Installation, Operation and Service Manual for Details)


Clearances to Combustibles**
Model
 
BH-40
BH-60
BH-80
BH-100
BH-115/125
BH-140/150
BH-175/200
   
HZ
45°
HZ
45°
HZ
45°
HZ
45°
HZ
45°
HZ
45°
Horiz.
45°
 
A
6
8
6
8
6
8
6
10
6
10
6
12
8
12
 
B
27
8
35
8
38
8
40
8
46
8
50
8
52
8
 
C
52
50
62
59
65
65
70
73
76
77
79
83
82
85
 
D
27
46
35
54
38
60
40
64
46
69
50
74
52
79